Section 2000: Grounds and Jumper Components

Click here to view .pdf version of catalog section.

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Bronze body, Smooth jaws, Bronze T-handle/eyescrew with fine threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 200 Amps
  • Fault Current - 15 Cycles: 21,500 Amps
  • Fault Current - 30 Cycles: 15,000 Amps

Mechanical Ratings:

  • Recommended Torque: 200 in-lbs.
  • Main Line Range - Maximum: 477 kcmil ACSR/.814"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 2

 

Catalog#
C600-1959

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamps

 
  • Bronze body, Smooth jaws, Bronze eyescrew - with fine threads, drilled terminal, no threads

Electrical Ratings:

  • Continuous Current: 200 Amps
  • Fault Current - 15 Cycles: 21,500 Amps
  • Fault Current - 30 Cycles: 15,000 Amps

Mechanical Ratings:

  • Recommended Torque: 200 in-lbs.
  • Main Line Range - Maximum: 477 kcmil ACSR/.814"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 2

 

Catalog#
T600-0466

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Bronze body, Smooth jaws, Bronze eyescrew - with fine threads, drilled terminal, no threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 350 in-lbs.
  • Main Line Range - Maximum: 1033 kcmil ACSR/1.25"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
C600-2271

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 

Aluminum body, Smooth jaws, Eyescrew handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 300 Amps
  • Fault Current Rating: ASTM Grade 3
  • Fault Current - 15 Cycles: 27,000 Amps
  • Fault Current - 30 Cycles: 20,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 2/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 1 lbs.
  • Jaw Opening - Maximum: 0.998"
  • Jaw Opening - Minimum: 0.128"

 

Catalog#
C600-1754

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 

Aluminum body, Serrated jaws, Eyescrew handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range -Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 1 lbs.
  • Jaw Opening - Maximum: 1.25"
  • Jaw Opening - Minimum: 0.128"

 

Catalog#
T600-2708

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Aluminum body, Smooth jaws, Bronze eyescrew with fine threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 1000 kcmil Cu., 1590 ACSR/1.50"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
C600-1743

MacLEAN POWER

Grounding Clamps

"C" Clamp

 

Features:

  • Can be installed on all electrical facilities, apparatus, tubes and conductors as well as various equipment (trucks, pulling equipment, etc.)
  • This universal clamp can also be used on a jumper cable
  • Installation on conductor, round bus bar and grounding ball stud of 20mm and 25mm
  • Thermal shock indicator changes color (from white to red) when the clamp reaches a temperature of 200°F
  • Stress-relief to reduce cable damage and serve as a shock damper if fault occurs
  • Locations on each side of the clamp for 20mm or 25mm grounding ball studs installation, which serve as support studs for either a grounding cluster or cascade assembly
  • Fitted to receive a 5/8"-11UNC threaded stud ferrule
  • Lubrication chamber for upkeep of threads
  • Installation eye for installing clamp with shotgun stick
  • Double internal threads for fast installation and removal

Material:

  • Aluminum Clamp and Keeper

 

Catalog#
01-M-036

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Aluminum body, Smooth jaws, Bronze eyescrew with Acme threads, 5/8"-11 UNC terminal thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 2" O.D. Bus
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-3/4 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
C600-2255

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Aluminum body, Serrated jaws, Eyescrew handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 1.75 lbs.
  • Jaw Opening Size - Maximum: 2"
  • Jaw Opeing Size - Minimum: 0.162"

 

Catalog#
C600-2256

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 

Aluminum body, Smooth jaws, Eyescrew handle, Pressure Terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 2.75 lbs.
  • Jaw Opening - Maximum: 2"
  • Jaw Opening - Minimum: 0.162"

 

Catalog#
C600-2281

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

"C" Clamp

 
  • Aluminum body, Serrated jaws, Bronze eyescrew with Acme threads, Bronze pressure-type terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 2" O.D. Bus
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 2 lbs.
  • ASTM Designation: Type 1, Class B, Grade 5

 

Catalog#
C600-2282

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Duckbill

 
  • Aluminum body, Smooth jaws, Eyescrew handle, Pressure terminal type

Electrical Ratings:

  • Continuous Current: 300 Amps
  • Fault Current Rating: ASTM Grade 3
  • Fault Current - 15 Cycles: 27,000 Amps
  • Fault Current - 30 Cycles: 20,000 Amps

Mechanical Rating:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 2/0 Cable w/ Plain Terminal
  • Jumper Range - Minimum: #2 Cable w/ Plain Terminal
  • Weight: 1.5 lbs.
  • Jaw Opening Size - Maximum: 0.574"
  • Jaw Opening Size - Minimum: 0.162"

 

Catalog#
G1810-2

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Duckbill-Type

 
  • Aluminum body, Smooth jaws, Bronze eyescrew with fine threads, Bronze pressure-type terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 566 kcmil Cu., 900 kcmil ACSR/1.162"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Plain Plug
  • Jumper Range - Minimum: #2 Grd. Cable w/Plain Plug
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
G3622-1

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Duckbill-Type

 
  • Aluminum body, Smooth jaws, Bronze eyescrew with fine threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 566 kcmil Cu., 900 kcmil ACSR/1.162"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
C600-1734

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Duckbill-Type

 
  • Aluminum body, Bronze upper jaw, Serrated jaws, Bronze eyescrew with Acme threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 950 kcmil Cu., 1510 kcmil ACSR/1.506"
  • Main Line Range - Minimum: #6 Sol. Cu./.162"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class B, Grade 5

 

Catalog#
C600-0197

MacLEAN POWER

Grounding Clamps

Duck Bill

 

Features:

  • Thermal shock indicator changes color (from white to red) when the clamp reaches a temperature of 200°F
  • 3/4-10 UNC double lead threads for strength and fast installation
  • Lubrication chamber for upkeep of threads
  • Stress relied to reduce cable damage and serve as a shock damper if fault accurs
  • Material: Aluminum

Specifications:

  • Weight: 1.2 lbs.
  • Jumper Cable Minimum: #2
  • Jumer Cable Maximum: 4/0
  • Dimensions: 6-7/8" x 5-1/2" x 2-7/8"
  • Main Conductor Minimum: 6 AWG (.16)
  • Main Conductor Maximum: 900 MCM (1.162)
  • Capacity 15 Cycles:

35 kA (IEC)*

50 kA (ASTM)*

* = IEC rating is Phase-Phase on 900 MCM conductor, ASTM rating is Phase-Ground on 900 MCM conductor

 

Catalog#
HCDB-117

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Tower & Flat-Face

 
  • Aluminum body, Serrated jaws, Bronze eyescrew with fine threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 25,000 Amps
  • Fault Current - 30 Cycles: 25,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 1-1/2" Angles, 1-1/2" Flat
  • Main Line Range - Minimum: 1/8"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type 1, Class B, Grade 3

 

Catalog#
C600-1735

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Tower & Flat-Face

 
  • Aluminum body, Serrated jaws, Bronze T-handle with Acme threads, 5/8"-11 UNC terminal threads

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 25,000 Amps
  • Fault Current - 30 Cycles: 25,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 1-1/2" Angles, 1-1/2" Flat
  • Main Line Range - Minimum: 1/8"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 1-1/2 lbs.
  • ASTM Designation: Type III, Class B, Grade 3

 

Catalog#
T600-1798

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Flat Face

 
  • Bronze body, Serrated jaws, T-handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 4 lbs.
  • Jaw Opening Size - Maximum: 1.5"
  • Jaw Opening Size - Minimum: 0.125"

 

Catalog#
C600-2231

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Flat Face

 
  • Bronze body, Serrated jaws, Eyescrew handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 3 lbs.
  • Jaw Opening Size - Maximum: 1.5"
  • Jaw Opening Size - Minimum: 0.125"

 

Catalog#
C600-2232

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Tower & Flat-Face

 
  • Bronze body, Serrated jaws, Bronze eyescrew with fine threads, Bronze pressure-type terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 25,000 Amps
  • Fault Current - 30 Cycles: 25,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 1-1/2" Angles, 1-1/2" Flat
  • Main Line Range - Minimum: 1/8"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Plain Plug
  • Jumper Range - Minimum: #2 Grd. Cable w/Plain Plug
  • Weight Each: 2-1/2 lbs.
  • ASTM Designation: Type 1, Class B, Grade 3

 

Catalog#
G3363-1

HUBBELL POWER SYSTEMS INC.

Sub-Station Bus Clamps

"C" Clamp

 

Aluminum body, Smooth jaws, Eyescrew handle, 5/8"-11 thread

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current Rating: ASTM Grade 5
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 4/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Weight: 2.3 lbs.
  • Jaw Opening - Maximum: 2-1/2"
  • Jaw Opening - Minimum: 0.232"

 

Catalog#
C600-1733

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Bus Bar

 
  • Aluminum body, Smooth jaws, Bronze eyescrew with Acme threads, Bronze pressure-type terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 300 in-lbs.
  • Main Line Range - Maximum: 4" x 4" Square, 4.5" O.D. Bus
  • Main Line Range - Minimum: 1/0 Str. Cu./.368"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Plain Plug
  • Jumper Range - Minimum: #2 Grd. Cable w/Plain Plug
  • Weight Each: 5-1/4 lbs.
  • ASTM Designation: Type 1, Class A, Grade 5

 

Catalog#
G3369

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

All-Angle

 
  • 5/8"-11 UNC Threaded Terminal

Electrical Ratings:

  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Main Line Range - Maximum: 2-1/2" IPS/2.88"
  • Main Line Range - Minimum: #2 Cu./.258"
  • Jumper Range - Maximum: 4/0 Grd. Cable w/Threaded Stud
  • Jumper Range - Minimum: #2 Grd. Cable w/Threaded Stud
  • Weight Each: 3-1/4 lbs.
  • ASTM Designation: Type 1, Class B, Grade 5

 

Catalog#
C600-1732

HUBBELL POWER SYSTEMS INC.

Penetrator Clamps

Ground Sets for Underground Cable

 

For temporary grounding of underground distribution cable with jacket over concentric neutral, special clamps help ensure contact with center conductor.

Spike-point clamp main-line capacity is 2-1/2".

 

Catalog#

Description

T600-1922

Spiked Clamp Only

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Ball Stud Clamp

 

With tapped terminal for threaded stud ferrule on #2 to 4/0 grounding cable

 

Catalog#
C600-2101

HUBBELL POWER SYSTEMS INC.

Standard Ball Stud
 

 

Catalog#
C600-2102

HUBBELL POWER SYSTEMS INC.

Long ball Stud
 

3" nominal shank length

 

Catalog#
T600-2364

HUBBELL POWER SYSTEMS INC.

Support Studs

Pressure-Terminal Clamps

 

These support studs can be installed on any pressure type terminal Ground Clamp, in place of the restraining strap immediately below the pressure terminal. The stud serves as a mechanical parking stand for a second clamp, preventing the clamp from making contact with the conductor or ground. This feature is particularly beneficial in three-phase grounding application.

 

Catalog#

Description

Size of Stud

G3626

Stud for Rear Mount

7/16 " x 2.5"

HUBBELL POWER SYSTEMS INC.

Cluster Bars

for Wood Poles and Tower Angles

 

Compact 5" aluminum-alloy bar accepts C-type or duckbill clamps for phase-to-phase grounding technique. Adjustable wheel binder and 36" chain for wood-pole applications. Hook style for attachment to tower angles.

 

 

Catalog#

Description

T600-1549

Pole-Mount Grounding Cluster Bar

HUBBELL POWER SYSTEMS INC.

Grounding Bar Assembly

Cluster Bar

 

Compact 5" aluminum-alloy bar (5/8" diameter) accepts C type or duckbill clamps for phase-to-phase grounding technique. Hook style for attachment to tower angles.

Specifications:

  • Product: Cluster Bar
  • Mount to: Tower Mounted
  • Continuous Current: 400 Amps
  • Fault Current - 15 Cycles: 43,000 Amps
  • Fault Current - 30 Cycles: 30,000 Amps
  • Weight: 10 lbs.

 

Catalog#
T600-1737

HUBBELL POWER SYSTEMS INC.

Terminal Blocks

4-Way

 

Chance terminal blocks are used to attach ground leads from grounding clamps to a common ground. These terminal blocks are also ideal where permanent temporary grounding sets are part of a substation emergency equipment. Accommodates 4/0 grounding cables with plain ferrules.

 

Catalog#

Description

G4754-1

Four-Way Terminal Blocks

HUBBELL POWER SYSTEMS INC.

Grounding Clamps

Cutout

 

Bronze clamp is used to ground the bottom hinge contact on cutouts used on distribution riser poles or where grounding is required. It fits these cutouts: Chance F2, F3, and C Cutouts; Westinghouse LDX, Southern States B-80; Series 63; Joslyn; S&C Type SX; McGraw-Edison LMO, and GE Durabute. Clamp can be installed with or without grounding cable to aid as a warning and possibly avoid accidental closing of cutout. Clamp's drilled terminal accepts threaded-stud cable ferrules. It also accepts threaded L-Stud and T-Stud Terminals (3/4" diameter bronze) for use with conventional ground-clamp cable sets.

Electrical Ratings:

  • Continuous Current: 300 Amps
  • Fault Current Rating: ASTM Grade 3
  • Fault Current - 15 Cycles: 27,000 Amps
  • Fault Current - 30 Cycles: 20,000 Amps

Mechanical Ratings:

  • Recommended Torque: 250 in-lbs.
  • Jumper Range - Maximum: 2/0 Cable w/ Threaded Terminal
  • Jumper Range - Minimum: #2 Cable w/ Threaded Terminal
  • Handle Type: Eyescrew
  • Weight: 2 lbs.

 

Catalog#
C600-0785

HUBBELL POWER SYSTEMS INC.

Grounding Stud Terminal

L - Stud

 

Electrical Ratings:

  • Continuous Current: 300 Amps
  • Fault Current - 15 Cycles: 27,000 Amps
  • Fault Current - 30 Cycles: 20,000 Amps

Mechanical Ratings:

  • Weight: 1 lbs.

 

Catalog#
C600-0841

HUBBELL POWER SYSTEMS INC.

Grounding Stud

T - Stud

 

Electrical Ratings:

  • Continuous Current: 300 Amps
  • Fault Current - 15 Cycles: 27,000 Amps
  • Fault Current - 30 Cycles: 20,000 Amps

Mechanical Ratings:

  • Weight: 1 lbs.

 

Catalog#
T600-2408

HUBBELL POWER SYSTEMS INC.

Ground Grids

Personal Protective

EQUI-MAT™
 

Complies with OSHA 1910.269 for equipotential requirements near vehicles, underground gear, overhead switches and in substations.

Portable, Lightweight, High Performance

The EQUI-MAT™ Personal Protective Ground Grid provides an easy way to help establish an equipotential zone for a lineworker to stand on during various energized and deenergized work pratices. Properly applied, it accomplishes compliance with Occupational Safety and Health Administration (OSHA) 1910.269.

The EQUI-MAT™ Personal Protective Ground Grid easily can be taken anywhere needed, is simple to use, maintain and store. It consists of a high-ampacity tinned-copper-braid cable sewn in a grid pattern onto a vinyl/polyester fabric. Cable terminals permit connecting the mat's grid in series with an electrical ground and the subject system component or vehicle. Simply rinsing with water comprises all the care the mat requires. The mat may be folded and stored in a tool bag to help keep it clean and protected. Complete instructions are included with each unit.

Easy to use, versatile to many applications

Padmounted Transformers and Switches

Complies with OSHA 1910.269 for protecting workers operating and maintaining padmounted transformers and switchgear. The proper use of EQUI-MAT™ Personal Protective Ground Grid in these applications creates an equipotential zone just as a cluster bar (chain binder) does in overhead grounding pratices.

Mechanical Equipment (Vehicles, etc.) Grounding

It also helps provide compliance with OSHA 1910.269 for protecting workers around mechanical equipment which could become energized, such as utility vehicles and portable generators. For proper application, EQUI-MAT™ Personal Protective Ground Grids are attached to the vehicle (for example) at locations where workers could contact the vehicle.

Overhead Distribution and Transmission Switches

EQUI-MAT™ Personal Protective Ground Grid can help eliminate step and touch potential. Connect it to the handle of an overhead switch and stand on it when opening or closing the switch.

Line Apparatus Work

Similar uses for installing, maintaining or operating regulators, reclosures, capacitor banks.

Suspect Substation Grids

If station ground mat integrity is questionable, apply the EQUI-MAT™ Personal Protective Ground Grid.

Simple to Join Multiples for Larger Areas

Cascading (or joining together) two or more mats is easy with the connecting tab and hardware furnished with each mat. So connected in series, the conductive grids become one. Whenever a larger area is needed, simply place lug connector tabs of two adjacent mats on the supplied bolt or threaded shank of a ball stud and secure with supplied washer and nut.

Each Basic Unit includes a Long Ball Stud and illustrated instructions.

 

Catalog#

Size

Single [1/4]" Perimeter Braid

C600-2850

58" x 58"

C600-2851

58" x 120"

C600-2852

120" x 120"

HUBBELL POWER SYSTEMS INC.

Ground Grids

Personal Protective Pre-Packaged Kits

EQUI-MAT™
 

Each Pre-Packaged Kit includes Ground Grid plus Ground Set T600-2841 and Storage Bag C417-0147.

 

Catalog#

Grid Size

C600-2989

58" x 58"

C600-2990

58" x 120"

C600-2991

120" x 120"

HUBBELL POWER SYSTEMS INC.

Cable Reels

Portable

 

Portable reel quickly pays-out/takes-up, helps keep ground sets clean and neat, ready for use. Handles are comfortable, turned aluminum. Lightweight unit can be carried to remote sites or tubular-steel frame can be U-bolted to deck or truck. Galvanized drum has ribbed flanges to resist flexing and beaded rims to eliminate sharp edges. Reel is for storage only. Cable and clamps should be removed completely from reel before use. Failure to do so could result in a dangerous voltage drop and violent mechanical reactions. A label on the unit gives this warning.

 

Catalog#
C417-6086

HUBBELL POWER SYSTEMS INC.

Ground Rods

Temporary

 

The Chance Screw Ground Rod provides a temporary ground where a system ground is not available. When installed, the 6' spiraled ground rod develops less resistance than straight ground rods. However, actual effectiveness depends upon soil properties. The reusable Ground rod is copper clad. The helix (spiral), handle and wing nut are bronze.

 

Catalog#

Description

G3370

Screw Ground Rod

HUBBELL POWER SYSTEMS INC.

Load Pick-Up Tools
 

This tool can be used to pickup loads and carry 250 Amps at 15KV. Rubber gloves should be worn while installing. The head has a floating washer to minimize conductor damage as the jaws are installed. The contacts are spring loaded and can be closed by pulling an insulated lanyard, putting the operator away from the tool during pickup operations. The contacts cannot be teased closed. The tool cannot be used as a load break tool as the operator cannot open the contacts while the tool is on the conductor. A fiberglass rod, attached to the end of the lanyard, is used to recock the contacts, but because it must be inserted through the head of the tool, the lineman must remove the tool from the conductor before recocking. An orange-tinted clear Lexan® housing permits easy visual inspection. A nylon handguard is used to keep the lineman's hand away from the energized area. By simply removing the two screws in the handguard, the tool can be disassembled for inspection and maintenance. All current carrying parts are copper or copper alloy and contacts are silver plated. The recommended 15KV jumper cables for this tool are #2 and 1/0. It is recommended that the Load Pick-Up Tool be inspected and cleaned after 25 operations or after 90 days. Clean all plastic parts with soft cloth, damp with ethyl alcohol only.

Specifications:

  • Main Line Range: .162" min.
  • Main Line Range: 1.165" max.
  • Continuous Current: 250 Amps
  • Weight: 6.4 lbs.

 

Catalog#
C403-1631

HASTINGS

Load Pick-Up Tools
 

The HASTINGS Load Pick-Up Tool can be installed with a shotgun stick or with rubber gloves. (In accordance with your company's safe work pratices.)

Both tools come completely self contained with cocking tool, firing lanyard, and safety latch. (Optional carrying case available.)

The Head Casting is an aluminum alloy and also serves as a storage port for the cocking tool.

Clear plastic housing below the head casting allows for quick, easy, and visual inspection.

Each tool comes complete with an Operating and Mainenance Manual.

Specifications:

  • Main Line Range Minimum : 6 Solid / .16 dia.
  • Main Line Range Maximum: 1033 MCM / 1.25 dia.
  • KV Rating: 29.2 KV max.
  • Current Rating: 300A max.
  • Unit Weight:

6600 - 5.9 lbs.

6605 - 6.2 lbs.

01-089 - 2.7 lbs.

Warning: These Load Pick-Up tools are NOT LOAD BREAK devices!

 

Catalog#

Description

6600

Load Pick-Up Tool/Cable

6605

Load Pick-Up Tool/Stud

01-089

Padded Carrying Case

HUBBELL POWER SYSTEMS INC.

Grounding Cables

Copper

 

Copper Grounding Cable is available in yellow and clear, is extra flexible for handling ease yet strong and tough for long wear. Jacketing is smooth, abrasion, weather and oil resistant in accordance with applicable ASTM Specifications, marked with AWG size approximately every 4 feet.

Yellow jackets are T-prene rubber compound with -20°F recommended low temperature. Clear jackets (which allow visual inspection of strand conditions) are ultraviolet-inhibited Poly Vinyl Chloride (PVC). Recommended low temperature for PVC-jacketed cable is 0°F.

Extra-flexible cables, because of their extra-fine strands, require termination ferrules when used with ground clamps.

 

Catalog#

Size AWG

Strands

Diameter

Approx. O.D.

Approx. Wt. (lb./1,000 ft.)

Yellow-Jacket Copper Cable

 

S6116

2

665

0.320

0.55

280

S6117

1/0

1045

0.410

0.66

425

S6118

2/0

1330

0.470

0.73

520

S6119

4/0

2109

0.590

0.87

760

Clear-Jacket Copper Cable

 

S6449

2

665

0.344

0.53

289

S7568

1/0

1050

0.445

0.63

520

S6450

2/0

1323

0.487

0.70

546

S6451

4/0

2107

0.616

0.84

841

HUBBELL POWER SYSTEMS INC.

Copper Ferrules

Threaded-Stud Type - Shrouded

 

Threaded-Stud type for topped or drilled grounding-clamp terminals. Shrounded threaded copper ferrules.

 

Catalog#

Burndy Die No. or equivalent Sect. A

Burndy Die No. or equivalent Sect. B

Cable Size, AWG

C600-2622

U165

U166

#2

C600-2623

U165

U168

1/0

C600-2624

U165

U-L

2/0

C600-2625

U166

U-L

4/0

HUBBELL POWER SYSTEMS INC.

Copper Ferrules

Plain-Plug Type - Shrouded

 

Plain-Plug type for pressure-type grounding-clamp terminals. Shrouded plain copper ferrules

 

Catalog#

Burndy Die No. or equivalent Sect. A

Burndy Die No. or equivalent Sect. B

Cable Size, AWG

C600-2630

U165

U166

#2

C600-2631

U165

U168

1/0

C600-2632

U165

U-L

2/0

C600-2633

U166

U-L

4/0

HUBBELL POWER SYSTEMS INC.

Copper Ferrules

Unshrouded

 

Unshrouded ferrules are available either factory-installed in pairs on any cable length specified or as separate individual units, the ferrules install simply with a hydraulic crimping tool. Complete illustrated installation instructions come with the ferrules and include a table for the crimping die sizes to use.

Specifications:

  • Material: Copper
  • Terminal Type: Threaded or Drilled
  • Weight: .50 lbs.

 

Catalog#

Cable Size

Continuous Current (Amps)

Fault Current - 15 Cycles (Amps)

Fault Current - 30 Cycles (Amps)

Seciton A Burndy Die Number

C600-2606

#2

200

14,000

10,000

U165

C600-2607

1/0

250

21,000

15,000

U165

C600-2608

2/0

300

27,000

20,000

U165

C600-2609

4/0

400

43,000

30,000

U166

HUBBELL POWER SYSTEMS INC.

Aluminum Ferrules

Unshrouded

 

Unshrouded ferrules are available either factory-installed in pairs on any cable length specified or as separate individual units, the ferrules install simply with a hydraulic crimping tool. Complete illustrated installation instructions come with the ferrules and include a table for the crimping die sizes to use.

Specifications:

  • Material: Aluminum
  • Terminal Type: Threaded or Drilled
  • Weight: .20 lbs.

 

Catalog#

Cable Size

Continuous Current (Amps)

Fault Current - 15 Cycles (Amps)

Fault Current - 30 Cycles (Amps)

Section A Burndy Die Number

C600-2602

#2

200

14,000

10,000

U165

C600-2603

1/0

250

21,000

15,000

U165

C600-2604

2/0

300

27,000

20,000

U165

C600-2605

4/0

400

43,000

30,000

U249

MacLEAN POWER

Copper Ferrules
 
  • All ferrules are filled with inhibitive grease to prevent humidity infiltration
  • Compression ferrules for 5/8-11 UNC threaded type terminal

Material:

  • 99.9% electrolytic tin-plated copper
  • Stainless steel hardware (nut and lock washer) and grease cap included

 

Catalog#

Cable Caliber

Compression Die Husky

Compression Die Burndy

Capacity 15 Cycles - IEC

01-M-038-35-2

2 AWG

HT41CE

U-164

12 kA

01-M-038-1/0

1/0 AWG

HT41CF

U-166

20 kA

01-M-038-2/0

2/0 AWG

HT41CF

U-166

22 kA

01-M-038-4/0

4/0 AWG

HT41CJ

U-168

35 kA

HUBBELL POWER SYSTEMS INC.

Jumper Cables

Rated Phase-to-Phase 15 kV, 25 kV, and 35 kV with EPR Insulation/Jacket

 

Extremely flexible even at low temperatures, this cable features an insulation/jacket combination resistant to abrasion, oil, heat, moisture and ozone. The natural orange color of this mold-cured ethylene-propylene-base coating imparts high visibility. For easy identification, AWG size and voltage rating are embossed at 4-foot intervals.

For extended service life, an extruded screen interfaces insulation and conductor. This strand screen improves voltage-stress control by adding dielectric strength and eliminating internal corona.

Insulation and conductor screen meet and exceed ICEA-NEMA standard S-68-516.

For easy handling in diverse conditions, conductors are extra flexible alloy-coated copper-stranded rope per ASTM B-189 or B-33.

Ampacity ratings are based on 90°C conductor temperature at 40°C ambient.

 

Catalog#

Size AWG

Stranding

Approx. Cond. Diameter

Approx. Cable O.D.

Approx. Ampacity Rating, AMPS

15 kV Cable

 

S10043

#2

259/No. 26

0.322"

0.779"

200

S10044

1/0

413/No. 24

0.404"

0.863"

260

S10045

2/0

273/No. 23

0.455"

0.914"

300

S10046

4/0

437/No. 21

0.602"

1.065"

400

25 kV Cable

 

S11272

1/0

413

0.404"

1.113"

260

S11273

2/0

266

0.450"

1.160"

300

35 kV Cable

 

S11274

1/0

413

0.404"

1.287"

260

HUBBELL POWER SYSTEMS INC.

Connector Assemblies

Jumper Ferrules for 15 kV, 25 kV, & 35 kV Jumper Cable

 

Copper Connector Assemblies are necessary to join cable and clamp together on Jumper Clamps or Load Pickup Tools only Threads are 5/8"-11 NC for all connectors. Each Catalog Number consists of a copper connector, nut and lockwasher.

 

Catalog#

Cable Size

Burndy Die No. or equivalent

No. of Crimps

C600-2598

#2

U165

2

C600-2599

1/0

U165

2

C600-2600

2/0

U165

2

C600-2601

4/0

U166

2

HUBBELL POWER SYSTEMS INC.

Jumper Clamps

25 kV Size - 400 AMP Capacity

 

The T601-0039 Jumper Clamp has the same polyethylene material in the handle as other Chance Jumper Clamps. The handle length below the handguard is 7-1/2". The 400 amp continuous current rating is based on using 4/0 Jumper Cable on the tap side.

 

Catalog#

Description

Main Line Range Max.

Main Line Range Min.

Jumper Cable Range Max.

Jumper Cable Range Min.

T601-0039

Single Clamp

477 ACSR (.833")

#6 Copper (.162")

4/0

#2

HUBBELL POWER SYSTEMS INC.

Jumper Clamps

35 kV Size (Large Jaws) - 400 AMP Capacity

 

The T601-0040 Jumper Clamp has a larger contact opening for use on larger conductor distribution lines. The handle length below the handguard is 8-3/8". Easy to assemble, the connector assemblies are interchangeable between the 15 & 25 kV Jumper Clamps. The 400 amp continuous current rating is based on using 4/0 Jumper Cable on the tap side.

 

Catalog#

Description

Main Line Range Max.

Main Line Range Min.

Jumper Cable Range Max.

Jumper Cable Range Min.

T601-0040

Single Clamp

954 ACSR (1.165")

#6 Copper (.162")

4/0

#2

SALISBURY

Jumper Clamps

Clear Plastic

Sure-lok™
 

The New Salisbury Sure-lok™ Jumper clamp is a revolutionary improvement over any other jumper clamp in the world. Featuring a ratchet type locking mechanism (patent pending), this is the only clamp available guaranteed not to loosen once installed on a line.

Loose Jumper clamps not only jeopardize your safety but can also cause fires and power outages. Even when torqued using wrenches or pliers, traditional clamps will eventually loosen from line vibrations and thermal cycling. This clamp tightens with a ratchet action using one hand, with no extra tools for a secure, positive connection. It can't come loose until you want it to. Pull and turn the locking knob and it loosens like any traditional clamp.

 

Catalog#

Main Line Range

Max. Amps Continuous

Rating

OAL Length (in.)

Weight (lbs.)

1786

477 MCM (.9"-.162")

400

36 kV 0-0

11.5

3.9

2116

954 MCM (1.25"-.162")

400

21 kV 0-GRD

11.5

4.9

SALISBURY

Jumper Clamps
SALCOR®
 

SALCOR® Jumper Clamp not only provides a superior grip, but also resists ozone cutting and tracking. Being molded of rubber, these handles are inherently impact resistant and extremely durable. The body and jaw are made from a copper base alloy. The lower ring contact is made of self lubricating bronze. Assemble jumpers with insulated jumper cable and 5/8"-11 NC threaded ferrules.

 

Catalog#

Main Line Range

Max. Amps Continuous

Rating

OAL Length (in.)

Weight (lbs.)

2260

477 MCM (.9"-.162")

400

36 kV 0-0

11.5

4.8