3M 7691-S-4-3G 7691-S-4-3G QT-III 3
Product image thumbnail 0
Product image thumbnail 1
$1,152.00/ea
Usually ships within 8 to 12 Days
EA
Adding...
Already a Customer? Log in to view your pricing
Manufacturer 3M
Mfg Catalog # 7691-S-4-3G
Irby Part # 3772196

Features

  • Provides a void-free seal to tape shield, wire shield and UniShield® power cables
  • High dielectric-constant material regulates the distribution of electric field stress
  • Suitable for outdoor applications
  • Integrated design allows for easier installation, while sealing compounds provide constant radial pressure

Specifications

  • Application: Cable Connection
  • BIL: 150 kV
  • Breakout Boot: Yes
  • Cable Insulation Outside Diameter Range: 0.50-0.70 in
  • Cable Insulation Outside Diameter Range (Metric): 12.7-17.8 mm
  • Cable Shielding: UniShield® - Wire Shield - Tape Shield
  • Cable Type: MV-90 - MV-105
  • Conductor Material: Copper - Aluminum
  • Conductor Size by Voltage: (5 kV, 100%) 1-3/0 AWG, (5 kV, 133%) 3-2/0 AWG, (8 kV, 100%) 2-2/0 AWG, (8 kV, 133%) 2-2/0 AWG, (15 kV, 100%) 2-1 AWG
  • Conductor Sizes: 2/0 AWG - 750 kcmil - 2 AWG - 250 kcmil - 500 kcmil - 350 kcmil - 1 AWG - 3/0 AWG - 1/0 AWG
  • Connector Included: None
  • Family: QT-III
  • Indoor/Outdoor: Outdoor Skirted
  • Insulation Level: 100% - 133%
  • Insulation Outer Diameter (Imperial): 0.66 in - 0.52 in - 0.58 in - 0.67 in - 0.59 in - 0.6 in - 0.7 in - 0.57 in - 0.65 in - 0.63 in - 0.61 in - 0.69 in - 0.68 in - 0.54 in - 0.51 in - 0.62 in - 0.64 in - 0.56 in - 0.55 in - 0.53 in - 0.5 in
  • Insulation Outer Diameter (Metric): 12.7 mm - 16.002 mm - 15.748 mm - 14.478 mm - 17.78 mm - 15.24 mm - 15.494 mm - 13.716 mm - 13.462 mm - 16.256 mm - 16.764 mm - 13.208 mm - 17.018 mm - 16.51 mm - 17.272 mm - 13.97 mm - 12.954 mm - 14.224 mm - 14.986 mm - 14.732 mm - 17.526 mm
  • Insulation Rejacketing: Yes
  • Lug/Stem Connector Included in Kit: No
  • Maximum Cable Outside Diameter: 2.80 Inch
  • Maximum Cable Outside Diameter (Metric): 71.1 mm
  • Maximum Installed Length: 12.25 in
  • Maximum Wire Gauge: 325mm²
  • Minimum Wire Gauge: 120mm²
  • Number of Conductors: 3
  • Number of Skirts: 4
  • Product Type: Splice
  • RoHS EU Comments: Contact 3M for information
  • Splice Type: Inline
  • Typical Splice Length: 33 in
  • Typical Splice Length (Metric): 838 mm
  • Voltage: 15 kV - 25 kV - 5 kV - 8 kV - 35 kV
  • Voltage Application: Medium Voltage

Overview

UPC 05400743682
Item Long Description 3M Cold Shrink QT III 7600 S 3G Series Termination Kit includes a skirted, 3 phase termination. It ensures a pliable, tight seal for tape shield, wire shield and UniShield power cables. The conjunction of high dielectric constant material and sealing compounds allows the termination to withstand voltages of 5 to 35kV.
GTiN 00054007436829
Type QT-III
Conductor Size 2/0 AWG
Applications Cable Connection
Cable Type Tape Shield; UniShield(R); Wire Shield
Family Brand Name 3M
Voltage 8 kV
Indoor Outdoor Outdoor Skirted

Your Product Lists

Log In or register for an account to gain access to the product groups feature!

You can create lists of products for regular needs, special projects, even use one as a wishlist.

Your Part Numbers

Log In or register for an account to assign your company part numbers to products!

No more memorizing or cross-referencing! Map your company's internal part numbers to items, then use your part numbers for searching and ordering.